Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!
Last seen: Jan 12, 2025
Hi Derek, What a result!!............Changed the pump connector to CNP4 and pump no longer runs unless required by DHW call for heat.........proved i...
@DerekM Hi Derek, I have not yet tried swapping the DHW pump connection over although as you have said and from looking through all online manuals...
@derek-m Thanks for your advice Derek.....my system is out of warranty with the installer so I think I will come clean and let them know I have fou...
@harriup The wiring is not correct and the DHW pump is running all the time the primary pump is running....see latest post to @derekm I only run t...
Hi Derek, Been back up in the loft (Big mistake that was)! , and traced cables from pumps to the FTC board As we suspected the FTC is not wired a...
Hi Derek....no wonder you were not at your peak with the amount of input you contribute to the forums. Your assumption of my query could be correct ...
Agree it looks a bit like a rat's nest!! I think I differ in that I have an external plate heat exchanger (not the internal coil )and the dedicated ...
Derek....if you zoom in I think the model no's can be seen but I can clarify the auto pump is UPM3 Auto L(think this is the heating circuit pump)........
The unit came all prewired and plumbed from Mitsubishi so it sounds like it has to be as you have said...I think I will give mitsubishi a call on this...
Hi Derek, Photos as requested, the pump without any obvious manual control is the one adjacent to the one with LED display(the one that data sheets ...
@Sun&Air...thanks for your comments......a lot of water has passed under the bridge since I posted back on page 5 so things have got a bit disjoi...
@derekm and everyone else 😄 I said that I would investigate in more detail what is happening with my full mitsubishi packaged system pumps and have ...
- 26 Forums
- 2,725 Topics
- 63.8 K Posts
- 998 Online
- 7,126 Members
Join Us!
Installer Finder
Degrees of Separation
Latest Posts
-
RE: Jokes and fun posts about heat pumps and renewables
@transparent I’ve heard that that is why American cars ...
By Toodles , 4 hours ago
-
RE: HeatGeek vs Octopus surveys: puzzling disparity - any ideas why?
Have either quote provided room by room heat loss calcu...
By Old_Scientist , 18 hours ago
-
RE: Heat Pump Servicing & Maintenance – Good Value or Rip-Off?
@old_scientist if you are going DIY then you may wan...
By Papahuhu , 2 days ago
-
RE: Indevolt Batteries UK Support & Info Thread
After a short while that was followed by the 'power war...
By JamesPa , 2 days ago
-
RE: Samsung heat pump - data cable issue
That's well done. Cable is the correct type (LIYCY = 2x...
By bobflux , 2 days ago
-
RE: Electricity price predictions
I agree, we will find out at the next budget whether th...
By Old_Scientist , 3 days ago
-
RE: Missing flow temperature in Heat Geek proposal
@editor I went through HG website, so should be ok for ...
By sttpd1917 , 3 days ago
-
Who did the Freedom Heat Pump cloud server and what did...
By Mars , 3 days ago
-
RE: Who's your electricity provider and what's your tariff?
Reading between the lines of what octopus are doing wit...
By JamesPa , 3 days ago
-
RE: Air to air bus grant installer anywhere
The through wall two hole ones have their place (listed...
By EtchedPixels , 3 days ago
-
I hope it goes ok, Hon can be hard to set up IF the sof...
By Graham Hendra , 3 days ago
-
@clockworks Hi, So there is a big difference between st...
By ASHP-BOBBA , 3 days ago
-
@editor wellvery comprehensive answer. I will get all i...
By Keithb , 3 days ago
-
RE: Advice on my Heat Pump Journey: Old Stone Built Detached Cottage
all good advice I will follow this up
By PaulC , 3 days ago
-
Heat of vaporization of water is 2.25 MJ/kg (0.625 kWh/...
By bobflux , 4 days ago