Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

Clockworks
@clockworks
Member
Trusted Member
Joined: Jan 22, 2025
Last seen: Jul 18, 2026
Topics: 4 / Replies: 55
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

I've got the WC curve set for 49 degrees at zero, 32 degrees at 16 outside. 6 degrees outside today, so it's flowing at 43 degrees. Rooms are all ...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

That sounds feasible. Assuming it's currently set at the default (-5 to +5), then it doesn't appear to be working in WC mode - it's currently stopping...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

I was going to look at Thermo Diff, but it said I had to shut down before I could even see what the current settings were. Would you suggest lowerin...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

Interesting. I'll have a trawl through the installation manual for the Ecodan, see if there's anything similar. I'm right down west, between Hel...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

Unfortunately Home Assistant only stores detailed historical data for 10 days, then it saves hourly data long term. I need to tweak the system to stor...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

The maximum flow temp has always been within a degree of what the WC curve has called for. Coldest day here since it was installed was between minus...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

It's not that I'm chasing low flow temperatures forcthe sake of it, more a case keeping the house at a comfortable temperature in the most economical...

1 year ago
Reply
RE: Ecodan Legionella cycle - immersion heater problem

Looking at the ASP flow temp, it does indeed switch over to the immersion at 50 degrees. I've spoken to the installer, and they will replace the...

1 year ago
Reply
RE: Ecodan Legionella cycle - immersion heater problem

I think the switching is because the thermostat in the immersion heater element is switching on and off because the water close to the element is reac...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

Ah, I see. I hadn't seen that option. The title's a bit misleading- "hourly" meaning "for one hour" rather than what I assumed "hour by hour" I've p...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

@gary Ah, OK. I find that way of doing it more confusing, as it doesn't show the actual time on the horizontal axis. I get your point about matching...

1 year ago
Reply
RE: Ecodan 6kW - is it "cycling", or normal operation?

@gary Not sure I understand what you are asking for?

1 year ago