@batalto - thanks, I will check the filter and report back. Before I check it, presumably you need to turn the heating and DHW off before doing it?
@batalto - it would be interesting to compare flow rates, given we have similar units. I haven't cleaned the gauze filter, the one adjacent to the hea...
Some measurements from 0800 this morning: Midea controller: ambient 11 LWT 41 RWT 35 capacity 0kW flow 0.83M3/H current 0A Room temps (design temp...
@cycleneil - no, its controlled by an on/off room stat in the kitchen, currently set to 21 degrees, kitchen design temp is 19 degrees, so most of the ...
The rads are actually Ultraheat branded, and the output per size varies slightly between different manufacturers. My installer went with a certain sup...
Exactly, that is why I am increasing thinking it is a compound problem, both the heat pump capacity is inadequate at low ambients and the heat that is...
I wasn't meaning to be harsh (and note that I chose a Midea over a Mitsubishi, for various reasons, including it must be said its low profile design b...
Current (0915h) flow/return temps and top middle rear panel rad temps: Midea controller: Ambient: 7; LWT 47; RWT 41 PHE pipework: Primary in 45; p...
This gets complicated. Firstly there is the nominal output, as listed in the catalogues, usually at a delta t of 50. A correction factor then has to b...
@derke-m - Argghhh!!!! The forum has just deleted my reply. very frustrating. 'Something went wrong with your submission' or words to that effect, and...
@derek-m - OK, here are some minute by minute readings, col head abbreviations as before, csv text format. Ambient throughout was 5 degrees: Time,LW...
@mookyfoo - Midea promote themselves as being value for money, based on economies of scale, they are a huge company. They also promote themselves on t...
- 26 Forums
- 2,300 Topics
- 51.6 K Posts
- 214 Online
- 5,965 Members
Join Us!
Podcast Picks
Latest Posts
-
All understood. Basically you are planning on creatin...
By JamesPa , 53 seconds ago
-
RE: Don’t Install a Heat Pump Until You Read This
The last bit of that is bad. Thats just badly (well ap...
By JamesPa , 7 minutes ago
-
Hi yes we have FTC 5 but no flow meter was supplied so ...
By @sand , 15 minutes ago
-
RE: Help me keep the faith with my air source heat pump installation
@jamespa no airflow problems definitely. primaries 28mm...
By AdamK , 46 minutes ago
-
RE: Electricity price predictions
Er not sure that is universally true. Mine is cheaper ...
By JamesPa , 1 hour ago
-
RE: Heat Pump on Flat Roof Low Frequency Noise from Detached Neighbor
1) talk to your neighbour, that's unacceptable noise, a...
By davidnolan22 , 1 hour ago
-
RE: Octopus Cosy Heat Pump Owners & Discussion Thread
Firstly you are getting your units mixed up which is a ...
By JamesPa , 2 hours ago
-
RE: Buffer tank bypass on EDF Ideal heat pump installation
I would bypass the buffer tank in one of flow or return...
By JamesPa , 2 hours ago
-
RE: British Gas vs Octopus Energy vs Heat Geek vs EDF vs Aira
I agree with all of that. 220 pages is perhaps 210-215...
By JamesPa , 2 hours ago
-
RE: Why Millions of UK Homes Struggle With Heat Pumps
One of those brilliant ideas that is obvious with hinds...
By Lenny , 3 hours ago
-
RE: 10kw heat pump run in 24*7 data?
Some observations: 1. I for one don't know the Vailla...
By cathodeRay , 3 hours ago
-
RE: Commencing on an ASHP Installation Process
Given that this thread ultimately turned out to be a di...
By Sheriff Fatman , 13 hours ago
-
Ecodan - Flow temperature spiking causing shutdown
Hi everyone, looking for some help. I am in a new bu...
By Gl3484 , 13 hours ago
-
Solis AI is on the right track to leverage the battery:...
By Batpred , 15 hours ago
-
RE: Grant 13kW Aerona3 - issues getting zones to temp
Thanks James, its honestly hard to keep it tog...
By Crimson , 16 hours ago
-
RE: Extend the colder range of the weather compensation curve?
Thanks for replies. That's good to hear and wanted to ...
By TheBinMan , 16 hours ago
-
RE: Air source heat pump roll call – what heat pump brand and model do you have?
Forum Handle: KevB Manufacturer: Ideal Model: 5kW ...
By KevB , 18 hours ago
-
RE: DHW heat loss through pumps.
Hi @ngillam I don't have anything as sophisticated for ...
By Marzipan71 , 20 hours ago
-
RE: Has anyone seen this problem before? Huge anticycling times
For the information of others. Vaillent came today, che...
By jamesh , 21 hours ago
-
RE: Here is my heat pump installation with questionable COP in Italy
Hi, and welcome to the forum. I cant quite u...
By JamesPa , 1 day ago