Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

adaml
@adaml
Member
Eminent Member
Joined: Dec 1, 2021
Last seen: Oct 27, 2023
Topics: 1 / Replies: 41
Reply
RE: Our Daikin ASHP

@derek-m No extras. The gas boiler is EHYKOMB33AA, the ASHP unit EVLQ05CAV3 and the controller EKRUCBL2.

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Hi Derek, Yes I would say you are correct, the ASHP was operating more in November when the outside temps were around 11-15°C and we cou...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m I've been playing around with the weather dependent curve; 45°C flow at -1°C and 30°C flow at 15°C then 50°C flow at -5°C an...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Hi Derek, yes definitely less than 5.11. November was 3.96 and December to date is 1.6.

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Hi Derek, That makes complete sense, sorry I think I had become too focussed on Possibility 1 and negated to spot the other option. ...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Got it - thank you! I think me reading it, understanding and knowing what is sensible are all different things. I can see though that @editor...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Thank you! This manual did not match my controller, however, this one does; The link doesn't seem to work, sorry - if you...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m I wonder if perhaps someone upstairs was running hot water - I will keep an eye on it. Thank you for these pointers. The installers man...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Thanks for your continued input, really appreciate it. The DHW is on demand from the gas boiler as we have no storage tank. I have noti...

4 years ago
Reply
RE: Our Daikin ASHP

That is very helpful, thank you. I'll spend some more time looking at this tonight and have set this to 5°C for now to stop the heat pump being used a...

4 years ago
Reply
RE: Our Daikin ASHP

Thanks Derek! The settings as they were for equilibrium temp (A.5.2) allowed the gas boiler to take over at temperatures below 15°C whereas the defaul...

4 years ago
Reply
RE: Our Daikin ASHP

Hello all, I am finding that the back up heating source (the gas boiler) is running more than the ASHP. I appreciate that temps have dropped but won...