Joining the Renewable Heating Hub forums is completely free and only takes a minute. By registering you’ll be able to ask questions, join discussions, follow topics you’re interested in, bookmark useful threads and receive notifications when someone replies. Non-registered members also do not have access to our AI features. When choosing your username, please note that it cannot be changed later, so we recommend avoiding brand or product names. Before registering, please take a moment to read the Forum Rules & Terms of Use so we can keep the community helpful, respectful and informative for everyone. Thanks for joining!

JamesPa
JamesPa
@jamespa
Moderator
Illustrious Member
Joined: Apr 3, 2023
Last seen: Aug 10, 2026
Topics: 27 / Replies: 5223
Reply
RE: Advice for a novice on Mitsubishi Ecodan 6kW

Doubtless its possible but Im not currently sure its necessary or even desirable. You have plenty of kit much of which is unnecessary and unhelpful, ...

7 months ago
Reply
RE: Heat pump not reaching flow temperature

That doesn't make much sense as it should alter the flow temp, that's what WC is. 0 and 15 are presumably the outside temps, what are the correspond...

7 months ago
Reply
RE: Octopus Cosy Heat Pump Owners & Discussion Thread

It does but it almost all applies to boiler systems and I wish I had understood when I had a boiler as much as I understand now. Just before I replac...

7 months ago
Reply
RE: ASHP Energy Consumption: Aira 12kW heat pump

Seriously? So 'our heat pumps just work, we don't know how, but trust us they do'. That sounds like a red flag of the highest order! No sorry tha...

7 months ago
Reply
RE: Ecodan with FTC7 - True Weather Compensation

Some data is definitely useful. I ordered the internet connection for my Vaillant heat pump and use Home assistant to pick up some basic data because...

7 months ago
Reply
RE: Installer Fitted 9kW Instead of 11kW Heat Pump and Changed MCS Paperwork - What do I do?

So theres a problem for starters. This means that the FT flatlines at -2 which means that, when its <-2 it isnt high enough to deliver the energy ...

7 months ago
Reply
RE: ASHP Energy Consumption: Aira 12kW heat pump

That seems high. Do you know what your WC settings are (even if you cant change them and even roughly?)  

7 months ago
Reply
RE: Ecodan with FTC7 - True Weather Compensation

Very much agree with this! Sometimes the way to get things to operate in pure WC mode is to set the curve on the controller, then just turn all the ...

7 months ago
Reply
RE: ASHP Energy Consumption: Aira 12kW heat pump

Thats sensible then   Most heat pumps seem to limit adjustment of the WC settings to installer mode, although some do expose something to ...

7 months ago
Reply
RE: Recommended home battery inverters + regulatory matters - help requested

Fair enough and Im not trying to circumvent regulation, I was just checking that I understood the underlying cause for your comment and that I hadn't ...

7 months ago
Reply
RE: ASHP Energy Consumption: Aira 12kW heat pump

Assuming your house was heated previously your oil consumption indicates a loss of more like 4-7kW, so an 8kW unit would probably have been perfect as...

7 months ago
Reply
RE: Recommended home battery inverters + regulatory matters - help requested

So thats a regulatory matter not technical? The Sunnyboy has no CT. If the CT for the battery inverter is on the incoming main then it does know th...

7 months ago