Sorry to be the bearer of bad news, your system is designed for a high temperature heat source, back boiler, on-off old type gas or oil boiler or biom...
@crimson Unfortunately unless you change the installation, anything you do will have little effect on the performance of the system. Heating systems a...
@crimson I know they would say that, all Grant is interested in is stopping their unit from suffering low flow errors, they do not care about you and ...
@crimson Possibly, but I still think it is a water flow issue looking at the pictures. You will find a huge difference removing the low loss header an...
@crimson You are fighting a loosing battle, the low loss headers and the high temperature zone valves are tying both arms and 1 leg behind your back. ...
Yes it does, a direct swap, same 4" hole. The mini is fine.
I helped develop these, they are brilliant, I have 1 in my house and no damp or condensation.
@abernyte It very much depends on how your system is designed and operated. The poorer the system and SCOP the less effect glycol has on the overall p...
This is correct but you have not calculated the pumping requirements correctly. You have forgotten the increase in viscosity of the glycol mixture. At...
SCOP 5.3, not even close to the UK record. 😀
🤣 🤣 Lets see if we can double that SCOP, I do not think we will be that far off from what I understand of the system 😊
- 22 Forums
- 2,096 Topics
- 46.1 K Posts
- 60 Online
- 3,383 Members
Join Us!
Trusted Installers
Struggling to find a reliable heat pump installer? A poor installation can lead to inefficiencies and high running costs. We now connect homeowners with top-rated installers who deliver quality work and excellent service.
✅ Verified, trusted & experienced installers
✅ Nationwide coverage expanding
✅ Special offers available
Latest Posts
-
RE: Commencing on an ASHP Installation Process
I couldn't see a way to detach one element from control...
By Sheriff Fatman , 3 minutes ago
-
RE: Mitsubishi cycling while on chilled water output
@jamespa you are so much faster than me, happy to see g...
By ASHP-BOBBA , 6 minutes ago
-
@jamespa Thanks for the advice - very helpful. I had al...
By abam48 , 10 hours ago
-
RE: Weather compensated secondary circuits with Biomass
Hi @andycoo we do an LK 110 standalone weather compensa...
By Sune , 11 hours ago
-
RE: Adding battery storage to SolarEdge PV system
@chandykris No need to apologise at all! I forgot to ad...
By Toodles , 1 day ago
-
RE: Say hello and introduce yourself
Yes please do Suggesting a loss in the region...
By JamesPa , 1 day ago
-
RE: Surface mount or bury primaries for heat pump installation?
Can we have some links to those you're considering plea...
By Transparent , 1 day ago
-
As I have reported elsewhere we turned on the cooling o...
By downfield , 2 days ago
-
@hughf, I think we’ll organise an RHH session at Instal...
By Mars , 3 days ago
-
@el3b Hi, sorry to hear that, it is advisable to instal...
By ASHP-BOBBA , 3 days ago
-
RE: Difficult positioning of air source heat pump
@rikiarn Out of intrigue, the thread reads as though Ai...
By Sheriff Fatman , 3 days ago
-
RE: Mitsubishi Ecodan Fails to Heat Water despite temperature drop
@m1kegibson If you are able to access the service me...
By HarriUp , 3 days ago
-
RE: When will heat pumps and install prices come down?
... which of course is impossible because the world mov...
By JamesPa , 3 days ago
-
RE: Battery storage to run Heat Pump.
I would be surprised if the battery chemistry is going ...
By Transparent , 4 days ago