RE: Creating a second zone on Mitsubishi Ecodan ASHP

Had another go at this, the morning. With SW2-7 ON it gives me a flashing LL error at the top of the main controller, but it still appears to run nor...

12 months ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

Thanks for your time with this Gary. I have a wireless controller running Zone 1. Sounds like the manual is more of a hindrance than a help! Your co...

12 months ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

Derek - thanks for that. Zone 1 was set to Room RC1 (I assume that's because I have the wireless thermostat ). I've changed it to main RC to see if ...

1 year ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

Gary -in the installation manual I'm looking at, on p26, 5.3. Functions Settings, under SW2-6. (mixing tank) it states that when SW2-6 is off 2 Zone t...

1 year ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

Still no joy! With SW2-6 and SW2-7 turned on I can see two zones and set Zone 1 sensor to be Room RC1 and Zone 2 to be mainRC (instead of TH1). Howe...

1 year ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

I had been doing that - the whole system was shut down between changes. But I hadn't made any changes to the main controller but it looks as if I can...

1 year ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

Thank you Derek and Gary. I'm using the wireless thermostat to control the temp for the rads and a third party one to control the UFH. So from the vi...

1 year ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

I take your point about a single zone -it has been running as a single zone but I'd like to try with more control. Also it has now become a challenge...

1 year ago
Reply
RE: Creating a second zone on Mitsubishi Ecodan ASHP

Thanks, Gary, - I've tried it with SW3-1 turned on - but still get the L5 error. I assumed that SW3-1 was purely to change the operation depending up...

1 year ago
Share:

Join Us!

Trusted Installers

Struggling to find a reliable heat pump installer? A poor installation can lead to inefficiencies and high running costs. We now connect homeowners with top-rated installers who deliver quality work and excellent service.

✅ Verified, trusted & experienced installers
✅ Nationwide coverage expanding
✅ Special offers available

👉 Find your installer now!

Latest Posts

x  Powerful Protection for WordPress, from Shield Security
This Site Is Protected By
Shield Security