RE: Samsung E911 intermittent issue

@netdonkey Should be shut of valves either side. the nut can be a bit tight on some of them, be sure to support the pipe when you try.

11 months ago
Reply
RE: New Samsung 12KW Heat Pump Help

@mike-h I will change my statement to: you cannot get 12kW or 10.4 or 9 Kw of heat down a 28mm pipe efficiently (this is not to say you wont get it ...

11 months ago
Reply
RE: New Samsung 12KW Heat Pump Help

@editor I would like to add further to the installers advice: I cant tell from the pipework in the picture but you will not get 12kW down a 28mm...

11 months ago
Reply
RE: Samsung E911 intermittent issue

@netdonkey The strainer can be anywhere on the rerun line from the airing cupboard / plant room to the ASHP condenser, so this could be in that room o...

11 months ago
Reply
RE: Samsung E911 intermittent issue

@netdonkey The model number for your Samsung indicates it is an 8kW system? The flow rates you are indicating only provide around 2.5kW and the code E...

11 months ago