RE: Our Daikin ASHP

@derek-m No extras. The gas boiler is EHYKOMB33AA, the ASHP unit EVLQ05CAV3 and the controller EKRUCBL2.

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Hi Derek, Yes I would say you are correct, the ASHP was operating more in November when the outside temps were around 11-15°C and we cou...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m I've been playing around with the weather dependent curve; 45°C flow at -1°C and 30°C flow at 15°C then 50°C flow at -5°C an...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Hi Derek, yes definitely less than 5.11. November was 3.96 and December to date is 1.6.

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Hi Derek, That makes complete sense, sorry I think I had become too focussed on Possibility 1 and negated to spot the other option. ...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Got it - thank you! I think me reading it, understanding and knowing what is sensible are all different things. I can see though that @editor...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Thank you! This manual did not match my controller, however, this one does; The link doesn't seem to work, sorry - if you...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m I wonder if perhaps someone upstairs was running hot water - I will keep an eye on it. Thank you for these pointers. The installers man...

4 years ago
Reply
RE: Our Daikin ASHP

@derek-m Thanks for your continued input, really appreciate it. The DHW is on demand from the gas boiler as we have no storage tank. I have noti...

4 years ago
Reply
RE: Our Daikin ASHP

That is very helpful, thank you. I'll spend some more time looking at this tonight and have set this to 5°C for now to stop the heat pump being used a...

4 years ago
Reply
RE: Our Daikin ASHP

Thanks Derek! The settings as they were for equilibrium temp (A.5.2) allowed the gas boiler to take over at temperatures below 15°C whereas the defaul...

4 years ago
Reply
RE: Our Daikin ASHP

Hello all, I am finding that the back up heating source (the gas boiler) is running more than the ASHP. I appreciate that temps have dropped but won...

4 years ago