Reply
RE: Removing a Low Loss Header from Samsung Gen6 System

also its worth saying, the PWM pump is not the enabler to run at low flow temps. That comes from having big enough emitters, properly balanced, etc. ...

1 month ago
Reply
RE: Removing a Low Loss Header from Samsung Gen6 System

@ecobaker mine did not need a firmware change. the PWM worked first time. I am not even sure how you would go about getting a firmware change done. ...

1 month ago
Reply
RE: Removing a Low Loss Header from Samsung Gen6 System

@bontwoody it will run at 35, but only stably if you have enough emitters to balance the min output of the HP. Which in my case with a 16kw gen6 unit...

1 month ago
Reply
RE: Grant 13kW Aerona3 - issues getting zones to temp

probably about a grand's worth as well. which could have been not spend during the original install. its not just for laughs that we keep banging on...

2 months ago
Reply
RE: Samsung Gen 6 Issues with outlet temp

@ecobaker you might want to check that the right valves are open and not open when wanted. I suggest drawing a plumbing diagram and a wiring diagram a...

2 months ago
Reply
RE: Samsung Gen 6 Issues with outlet temp

@ecobaker the description of what the system did makes total sense if there was nothing running round the rads. as you have an LLH you need the second...

2 months ago
Reply
RE: Daikin Altherma ASHP technical specs

physics says that if you know what flow rate the existing circulation pump is running at, its power level, and the characteristic curve of the pump (w...

2 months ago
Reply
RE: Samsung Gen 6 Issues with outlet temp

there is one G6 8kw on HPM.org, here , low point seems to be about 2.5kw. The owner of that one might be on this board as well, I can't remember. ...

2 months ago
Reply
RE: Samsung Gen 6 Issues with outlet temp

@ecobaker so... your points, summarised. the guides you need are all here. type MIM-E03CN into the search. the MIM controller manual has all the p...

2 months ago
Reply
RE: Single vs. three phase for heat pump, EV and appliances

@editor I did look at 3 phase, it was painful, got quoted 10k just for the DNO piece. and that was for tapping into the phases that's only 5 metres aw...

2 months ago
Reply
RE: Installing your own ASHP

@jamespa I was wondering if you might say this 🙂 . those who've self installed have , generally speaking, installed in such a way that is compliant ...

2 months ago
Reply
RE: How can I programme a setback for my Samsung Gen6 8kW heat pump?

@ecobaker if its in the airing cupboard it'll be no use, you need to move it to a living space to use it as the stat. Two wire low voltage so easy to ...

2 months ago