Reply
RE: Heat pump's integral circulator pump

@ubert767 File is attached. My explanation may be a bit unclear. My HP only turns off when all stats turn off, otherwise the flow modulates above ...

3 months ago
Reply
RE: Heat pump's integral circulator pump

@ubert767 You have a UFH system and house size similar to mine except I have a Samsung Gen 4 Split 4kW. You were wise and chose a split system which i...

3 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@sunandair This new Ecodan validates your argument about following WC closely for maximum efficiency. You can now set your design flow and radiator si...

3 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@jamespa Quoted performance figures @35C flow, -7C OAT = 8.2kW and @25C flow, 15C OAT = 2.1kW. Quite something. Other output models as well.

3 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@jamespa I agree. That is where the design choices come in. You have to design within the constraints imposed on you, realistic or not.

3 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@jamespa It is all about design choices. In my view heating at extreme low end temperatures is a small minority of overall heating which might not eve...

3 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@sunandair Posted by: @sunandair "If the weather curve is set correctly then the house envelope will never reach the set temperature and therefor...

4 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@sunandair I think I understand what you are getting at with “widest range”. This is not an easy dilemma. You are right about radiator over-size at 15...

4 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@sunandair Regarding radiators, UFH and WC, system design can have some quirks. Say one designs for the following:i) -3C design temperature with a mat...

4 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@uk_pete_2000 I am now totally confused how your minimum output 6kW heat pump is coping with <3kW load without serious cycling, but never mind. R...

4 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@uk_pete_2000 In the light of this discussion, could you maybe share what is happening on your system as you have a 13kW heat pump in a low-loss passi...

4 months ago
Reply
RE: Controversial opinions - pure weather compensation, buffer tank, heat loss, oversized heat pumps

@uk_pete_2000 Your u-values stack up with the amount of insulation installed. I presume therefore that you also have MVHR. As the peak heat load is wa...

4 months ago
Page 9 / 10
Share:

Join Us!

Trusted Installers

Struggling to find a reliable heat pump installer? A poor installation can lead to inefficiencies and high running costs. We now connect homeowners with top-rated installers who deliver quality work and excellent service.

✅ Verified, trusted & experienced installers
✅ Nationwide coverage expanding
✅ Special offers available

👉 Find your installer now!

Latest Posts

Members Online

x  Powerful Protection for WordPress, from Shield Security
This Site Is Protected By
Shield Security