@robl I've added the screens. Li-Bms screen is accurate. Sunsynk screen shows a +0.3V difference between it and battery. Also shows voltage s...
@robl Ill take a photo of the screen tonight & also in AGMV mode - From memory, it is set to 56.7V - Unless i factory reset/run it in AGMV ...
@chickenbig Sunsynk support claims that Pylontech is not supported. Tho the BMS screen on the inverter is properly populated with the correct...
SITREP #5 No improvement on the system. Everyday, it is charging 1% less. Today was 84% then stopped charging. User timer set to 100%SOC. I'm ...
@misterb @vaugi OK, I'll contacted Fogstar Were I fall down that it is the battery - is that when the Sunsynk is factory reset - it charg...
@misterb @robl SITREP #4? Blimey, what haven't I tried Voltage mode, wasn't working very well. It's a bad SOC replacement. I tried every single...
Interesting review. Good timing for myself. Will be driving one shortly - how did you find space in the i4 - anyway bigger than expected?
SITREP #2 Progress, but not logical progress on the Sunsynk. So I changed the Sunsynk over to AGM-V Good - I was able to charge to 100% and...
Hey I ran active balancer for the first 3 cycles. Voltage on the screen looks in good shape per cell. Figuring out the Sunsynk however......
Ok, I have ths mode turned on. How did you know what voltages to set on the inverter?
SITREP 1. Evening charging seems fixed. Adjusting the shutdown, low battery and restart fixed that. Apparentl y the inverter wil...
Grid Charge in battery setting is the 1 I suspect. Note - tried many setting to get it to stop charging this evening. I don't think I'd bu...
- 25 Forums
- 1,429 Topics
- 30 K Posts
- 24 Online
- 1,215 Members
Join Us!
Latest Posts
-
RE: Making best use of Agile with a battery and ASHP
Hello Jamesw, I’m in a similar situation as I have 8.1 ...
By Toodles , 4 hours ago
-
RE: Is this a bad installation and is there something wrong with my Samsung heat pump?
@kenbone no need for what kenbone regarding the 100watt...
By David999 , 1 day ago
-
RE: Insulation of flow and return Heat Pump piping
@mike-h Thanks Mike. Toodles.
By Toodles , 1 day ago
-
RE: Bivalent (or even trivalent!) system design options for a new GSHP installation
For your interest @algienon this is what happens when a...
By Transparent , 1 day ago
-
RE: Rising Damp – Production Recommendation
Yet another topic I'm not an expert in. Nonetheless, th...
By Majordennisbloodnok , 2 days ago
-
RE: Noise problems with newly installed Samsung 8kW ASHP
@editor yes, the more I read the forum posts the more I...
By sjn , 2 days ago
-
RE: Observations on my Ecodan's estimates of energy consumed and delivered
As it is possible for the FTC to be powered from a sepa...
By HarriUp , 2 days ago
-
RE: ASHP Cut-off Temperatures: What's Your Setting and is a Your Heating Still On?
My system has been running 24/7 on weather compensation...
By HughF , 2 days ago
-
RE: Heat Pump Truth or Myth#2 - Cycling uses a lot of power and ruins your COP
I cannot state that I have noticed that our A2A heat pu...
By Derek M , 2 days ago
-
RE: Maximising Savings: Navigating My First Year with Octopus Energy and Heat Pump Running Costs
@toodles I can also happily report that the Agile tarif...
By Steve D , 2 days ago
-
@editor As we all know, RHH always strive to educate, e...
By Toodles , 2 days ago
-
@bontwoody I used the website link to contact them for ...
By Toodles , 2 days ago
-
RE: Samsung ASHP power cycling
I have considered that and I would have expected to see...
By Blaine_t , 2 days ago
-
RE: 14kW Midea ASHP in an old leaky building
Hi @batalto. I see you have a Midea ASHP and I am sched...
By Kbedders , 2 days ago
-
RE: Additional ASHP kW for DHW cylinder?
We're in a similar boat to you with a hodgepodge of dif...
By Mars , 3 days ago
-
RE: No-code, plug-and-play monitoring for your heat pump
Anyway, so far we have all missed the main protagonist ...
By Toodles , 3 days ago
-
RE: Are Octopuses Slowing Consumer Adoption of Heat Pumps?
@ivanopinion Im in the same team as Ivan. I think for a...
By bontwoody , 3 days ago
-
RE: Issues with Vaillant connectivity via the MyCONNECT gateway
@drew-pa I don't know about hard work! It is pretty cl...
By dr_dongle , 5 days ago
-
RE: Are Solar Diverters Necessary for Homes with ASHPs and Solar PV?
@editor No, I made one 😀 Loft insulation all...
By Andris , 5 days ago
-
@hughf Thanks for that. Ah so they are talking about ...
By IRMartini , 5 days ago
Latest Topics
-
Making best use of Agile with a battery and ASHP
By jamesw 7 hours ago
-
By Toodles 2 days ago
-
By Blaine_t 2 days ago
-
Insulation of flow and return Heat Pump piping
By Toodles 3 days ago
-
Rising Damp – Production Recommendation
By Mars 3 days ago
-
Additional ASHP kW for DHW cylinder?
By Project_Electrify 3 days ago
-
By IRMartini 5 days ago
-
Riello / Midea - modbus set flow temp
By stuartornum 6 days ago
-
Ecodan software update. Real or scam?
By Morgan 7 days ago