I also struggle with some of LG's descriptions in the manual which I believe may have been written by some form of sadist. My interpretation would b...
I did look at swimming pool heat pumps some time ago, since like A2A heat pumps, they are much cheaper, probably because they don't qualify for the go...
@andyj LG apparently call Weather Compensation (WC) 'Seasonal auto temp.', see page 123 of attached manual. Correctly adjusting the WC is not a 5 ...
Since a heat pump is merely a device for producing thermal energy, I don't see any problem on the face of it. Obviously it would only work effectively...
I believe that a PWM capable water pump will default to maximum speed if the PWM signal is not present. You therefore probably have three choices, obt...
If the Indoor Air Temperature (IAT) is holding steady at 18C, then the Weather Compensation (WC) curve is set too low. Try increasing the WC setting u...
@kev-m Thanks Kev. I will hopefully have time tomorrow to run some tests.
@kev-m A couple of further questions. When do you heat DHW? How much other electrical energy do you use that may be adding to the heating?
@kev-m Thanks Kev, I don't seem to be able to locate the PM'd messages. What are the WC settings and do you have anti-freeze, and if so, at what c...
That is why I suggested an Uninterruptible Power Supply (UPS). Most critical system within an industrial system would normally have some form of UPS.
I remember you sending a post providing details about your system, but I don't seem to be able to find it. Would you mind posting the details again?
I suppose that it depends upon your maximum instantaneous load and how long a power cut or interruption may last. There are battery storage systems ...
- 26 Forums
- 2,364 Topics
- 53.6 K Posts
- 162 Online
- 6,027 Members
Join Us!
Worth Watching
Latest Posts
-
Sadly, no, @agentgeorge. The inverter will handle 5kW t...
By Majordennisbloodnok , 10 hours ago
-
RE: New Fogstar 15.5kWh upright solution
@transparent The readings are 0 for amps, 0 ...
By Batpred , 11 hours ago
-
RE: Say hello and introduce yourself
@velcro welcome to the forums. Please feel free start a...
By Mars , 11 hours ago
-
RE: Speedcomfort radiator fans
I watched the video to see whether they'd potentially b...
By Sheriff Fatman , 12 hours ago
-
RE: Mitsubishi Ecodan R290 10kW performance
@ecoste For what it's worth, this is my equivalent data...
By Sheriff Fatman , 12 hours ago
-
Daikin EDLA11D3V3 DHW Settings
I have a newly installed EDLA11D3V3 which I'm still get...
By Velcro , 12 hours ago
-
RE: Setback savings - fact or fiction?
Will come back to the above points, but for now, I've j...
By cathodeRay , 13 hours ago
-
@jamespa I have found that it comes as a shock when we ...
By Toodles , 14 hours ago
-
RE: My Powerwall 3 Consumes 3-4 kWh/Day in Self-Consumption: Is This Normal?
I suspect a good chunk of the "losses" are power consum...
By Bash , 15 hours ago
-
RE: Need Help Optimising My Rushed ECO4 Install: 12kW Bosch Heat Pump
Hi @mickamills . Welcome to the forum. It sounds like...
By bontwoody , 16 hours ago
-
RE: Midea ASHP – how to set weather compensation
@curlykatie did you get sorted with this?
By MickaMills , 16 hours ago
-
RE: External pipework insulation
@transparent I hope you are not being admonished @trans...
By Toodles , 16 hours ago
-
RE: Octopus Cosy Heat Pump Owners & Discussion Thread
The FT levels off at either the set point OR the minimu...
By AndrewJ , 2 days ago
-
RE: MyVaillant Connect Regular Disconnect
Thanks. Yes, if the time is consistently 11pm every nig...
By buckwem , 2 days ago
-
RE: Who's your electricity provider and what's your tariff?
@transparent Thanks, this helps. Could it be that St...
By Batpred , 2 days ago
-
RE: Clivet ASHPs and weather compensation
Simon did share a lot of very helpful advice. On furthe...
By ambris , 2 days ago
-
-
RE: Advice on internal circulation pump noise
Extend the primary branch and make sure you have more t...
By ASHP-BOBBA , 3 days ago