Reply
RE: Keystone COPs? I'm not getting the efficiencies I expected on my Ecodan.

@scrchngwsl so would it be fair to say while the HP is modulating to a reducing temperature, eg. to the set back temperature of say 16c down from 21c ...

2 years ago
Reply
RE: Keystone COPs? I'm not getting the efficiencies I expected on my Ecodan.

@scrchngwsl well spotted you’re absolutely right. I must have read .17 as bigger than .4 So possibly a lower setback, may also favour a Good COP? t...

2 years ago
Reply
RE: Keystone COPs? I'm not getting the efficiencies I expected on my Ecodan.

@mjr Put like that we do expect a lot…. - A constant room temperature when all the other parameters are constantly changing 😂😂👍

2 years ago
Reply
RE: Keystone COPs? I'm not getting the efficiencies I expected on my Ecodan.

Or is it “Good COP bad COP”? there’s something of a deception when looking at COP alone IMO. when we first powered up our heat pump we were using...

2 years ago
Reply
RE: Ecodan Controller Placement?

I got my installer to relocate my controller and replace my 3rd party (on off) room stat with the wireless Mitsubishi which is now set up as the room ...

2 years ago
Reply
RE: Mitsubishi Ecodan - Hot Water Settings

I can sense your frustration with the equipment and are looking for a quick solution but these issues may be connected in some way. So it would hel...

2 years ago
Reply
RE: Ecodan. How to run this efficiently with zero understanding.

Not sure but it seems to me that your primary return water isn’t rising much at all. Your DT appears to be getting wider and wider as the flow water r...

2 years ago
Reply
RE: Ecodan. How to run this efficiently with zero understanding.

Thanks for the explanation @derek-m that’s really useful 👍🏼

2 years ago
Reply
RE: Ecodan. How to run this efficiently with zero understanding.

Hello can enybody tell me what 0.9 MPS actually stands for in this heat geek cheat sheet. I thought it was Metres per second but that seems too bi...

2 years ago
Reply
RE: Ecodan. How to run this efficiently with zero understanding.

This is great information from everyone. Thanks all. Just as a total aside and completely non technical. Has anyone suffered with flow rate problems, ...

2 years ago
Reply
RE: 15mm piping and the need for flow separation

The min and max flow rate for the 12kW Samsung Gen6 is 12 & 58 lpm respectively, so I am interested in how you avoid 911 errors running below the ...

2 years ago
Reply
RE: 15mm piping and the need for flow separation

I’ve been evaluating the similar option for my 8.5 heat pump. Although your model is different to mine Several things in the info you have given sugg...

2 years ago