RE: Ecodan Room Temperature Mode

@damijand sorry, then I don't know why room temp isn't displayed. I'll ask on another group I'm on and let you know.

2 years ago
Reply
RE: Ecodan Room Temperature Mode

You may have to change the sensor settings in Initial Settings. I'm not at home so I can't check mine to see which it needs to be. I think you need ...

2 years ago
Reply
RE: Noob question - sizing of heat pump

The ones that can deliver what it says on the badge when it's cold outside will be able to deliver more under the right conditions. A 14kW Ecodan wil...

2 years ago
Reply
RE: Noob question

A Samsung HHSM- G600016-1 won't produce anything like 16.6kW at -3. The link below suggests more like 12-14kW at these low temperatures. You s...

2 years ago
Reply
RE: Ecodan Room Temperature Mode

@damijand the PAC-SE41TS-E is the one I meant. Although it's wired it comes with a long cable. If you want wireless, you'll need a PAR-WR51R-E and...

2 years ago
Reply
RE: Interesting? - ASHP from British Gas.

Love them or hate them, we need companies like BG (and Octopus) involved to move ASHPs into the mass market. It is interesting that if not wholeheart...

2 years ago
Reply
RE: Help required with Mitsubishi engineer report...

I don't know why an oversized ASHP would mess up Melcloud reporting. I think the Melcloud consumption is measured; it's the delivered that's estimate...

2 years ago
Reply
RE: COP for DHW using a heat pump

What you also need to remember is that when the heating is off, all the fixed overheads of keeping the ASHP on standby, running the controllers and al...

2 years ago
Reply
RE: Help required with Mitsubishi engineer report...

I'm assuming you don't have a hot tub or swimming pool or EV you haven't mentioned and it is the case that your AHSP is using most of the 14,000 kWh. ...

2 years ago
Reply
RE: COP for DHW using a heat pump

Just over 2 for me too but that's for a whole year. Ecodan with new 250l tank.

2 years ago
Reply
RE: Mitsubishi 8kW - strange energy use readings

Based on mine, I suspect your losses from the HW tank are as expected. It's not going to cost much; mine costs less than 2kWh per day to maintain tem...

2 years ago
Reply
RE: Mitsubishi 8kW - strange energy use readings

@westkent It will lose heat through the tank insulation as well as the pipes. The pipes will make a small but significant difference. Your tank i...

2 years ago
Page 11 / 107
Share:

Join Us!

Heat Pump Dramas?

Thinking about installing a heat pump but unsure where to start? Already have one but it’s not performing as expected? Or are you locked in a frustrating dispute with an installer or manufacturer? We’re here to help.

Pre-Installation Planning
Post-Installation Troubleshooting
Performance Optimisation
✅ Complaint Support (Manufacturer & Installer)

👉 Book a one-to-one consultation now.

Latest Posts

x  Powerful Protection for WordPress, from Shield Security
This Site Is Protected By
Shield Security