RE: ASPH Sizing Confusion

If you have a smart meter and gas heating, you have in principle very accurate data on demand. It's not entirely easy to interpret, and some addition...

2 years ago
Reply
RE: ASPH Sizing Confusion

Thermodynamically it must be less efficient to cycle than not to cycle, because a higher flow temp is required to achieve the same output from the emi...

2 years ago
Reply
RE: ASPH Sizing Confusion

Generally I agree wholeheartedly with your sentiment. However excessive oversizing can lead to other problems. One of the MCS contractors who did a...

2 years ago
Reply
RE: ASPH Sizing Confusion

Imho the biggest problem is to determine 'right size'. The spreadsheet models, even if used correctly, make several more or less unverifiable assumpt...

2 years ago
Reply
RE: ASPH Sizing Confusion

I just re-read your post and noticed this which I missed first time round. The answer is a definite 'no'. The approach to 'name plate ratings' varie...

2 years ago
Reply
RE: Heat pumps and on/off working - starting to quantify it

@derek-m Thanks, I look forward to 'playing'.

2 years ago
Reply
RE: ASPH Sizing Confusion

@bontwoody @squiff Also you must check the manufacturers capacity tables at the design OAT and FT. Some manufacturers 'name' their heat pumps very ...

2 years ago
Reply
RE: Heat pumps and on/off working - starting to quantify it

I think that there are broadly two main use cases of interest namely 'in all day' and 'out all day'. Obviously this ignores more complex shift patter...

2 years ago
Reply
RE: Heat pumps and on/off working - starting to quantify it

I think this is easily made intuitive by considering the limit situation, namely a building with zero thermal mass. In such a building it's obvious t...

2 years ago
Reply
RE: Heat pumps and on/off working - starting to quantify it

Good question! The total used over the year will be the sum (mathematically the integral) of the instantaneous, so on this interpretation they are s...

2 years ago
Reply
RE: Heat pumps and on/off working - starting to quantify it

A deceptively simple and important question but not actually that easy to calculate (for the avoidance of doubt I don't think the previous answer was ...

2 years ago
Reply
RE: My horrific Samsung heat pump installation and experience

Science advances through a combination of theory and experiment. True also with engineering. Fitting an equation (to experimental data) is only one ...

2 years ago