RE: Ecodan 11.2kW with low 5 litre per minute flow rate leading to L9 error

Fixed by the installer. It was a filter blockage, this filter was within the ASHP unit outside. A piece of plumbing sealant, must have worked its way ...

4 months ago
Reply
RE: Ecodan 11.2kW with low 5 litre per minute flow rate leading to L9 error

Hi Jake, yes I have an external pump too. It's set to 3, and both DHW and heating are set to 5. I experimented putting DHW and heating to 4, the flow ...

4 months ago
Reply
RE: Ecodan 11.2kW with low 5 litre per minute flow rate leading to L9 error

I've just cleaned the filter with the magnetic rod, there was some black bits in there but not a lot. I found a few YouTube videos suggesting there ma...

4 months ago
Reply
RE: Ecodan 11.2kw Low 5l flow rate

It did overnight with an L9 error, 1st time, I can reset it, it runs for an hour and then same error again which led me to check the flow rate. Pressu...

4 months ago
Reply
RE: EcoDan Cold Radiators

So I bled the radiators, I switched my programme back to fixed flow 40C and within 12 hours all radiators were hot again. So there's no blockages. I h...

6 months ago
Reply
RE: EcoDan Cold Radiators

@derek-m I have 2x UFH manifolds with 2x heatmisers with 4x motorised valve (ground floor and upper floor). 2x motorised valves on the cylinder, 1x mo...

6 months ago
Reply
RE: EcoDan Cold Radiators

@derek-m I can understand that, but with thermostats for each UFH room, wouldn't once they reach temperature then turn off and the water flow would be...

6 months ago